(Your shopping cart is empty)

  Home > Commercial Equipment >

15 Ton Rheem 208/230V or 460V 3 Phase VFD Air Handler, RHCLA2180
15 Ton Rheem 208/230V or 460V 3 Phase VFD Air Handler, RHCLA2180
 


Availability: Usually Ships in 2 to 3 Business Days
Product Code: CALL172668

Crating


We highly recommend crating your system. This item is highly susceptible to damage, crating has proven to help prevent damage & overall better customer satisfaction. When not crated, mishandling is probable
Choose Electrical


Commercial Heat Strip

Match Electrical & Size Desired*:


Qty:  
Description Technical Specs
 

15 Ton Rheem 208/230V or 460V 3 Phase VFD Air Handler, RHCLA2180


RHCLA Rheem Commercial Air Handler

Features:

  • CABINET - The pre-painted, sheet-metal cabinet uses 18-gauge material for structural components with an underlying coat of G60 electro deposition powder coating that is tested to withstand a rigorous 500-hour salt spray test, per ASTM B117.
  • MOTOR - Inherently protected motors are mounted inside of insulated cabinet to reduce motor noise. A choice of motor horsepowers and drive combinations are available to allow you to meet specified CFM at various static pressures up to 2" [.498 kPa] external static pressure.
  • LOW PROFILE - Allows for horizontal installation in most standard drop ceiling applications, and the movement of units through most standard doorways for addition or replacement work.
  • THERMAL EXPANSION VALVES - Standard all models.
  • FILTERS - One inch [25 mm] throwaway filters are standard, but filter racks are designed to accept either one inch [25 mm] or two inch [51 mm] filters. MERV 13 & MERV 8 filters are available as an accessory.
  • EVAPORATOR COIL - Two circuit, interlaced row split coils are constructed with copper tubes and aluminum fins mechanically bonded to the tubes for maximum heat transfer capabilities. All coil assemblies are leak tested up to 450 PSIG [3100 kPa] internal pressure prior to installation into units.
  • VARIABLE FREQUENCY DRIVE - Provides 2-stage airflow for improved part load efficiency. Meets California Title 24 requirements.
  • REFRIGERANT CONNECTIONS - Field piping connections are made through a fixed post between two side access panels on either side of the unit. Allows flexibility to meet most field conditions as well as full accessibility after the installation is complete. Units may be used with two straight cool condensing units or single circuit manifolded in the field using the copper fittings shipped with each unit.
  • DRAIN PAN - The galvanized steel drain pan is designed to trap condensate in either vertical or horizontal installations. Condensate drain connections are located on both sides of the unit allowing complete flexibility to meet most field conditions.
  • SERVICE ACCESS - Two removable panels on top and each side of the unit are easily removed for access to motors, blowers, sheaves, and filters.
  • HORIZONTAL OR VERTICAL - All models are designed for either application and can be installed in either position as supplied from the factory.
  • TESTING - All units are run tested at the factory prior to shipment. Units are shipped with a holding charge of nitrogen.